IFM PN7094 PN-010-RER14-QFRKG/US/ /V Pressure sensor with display IFM PN 7094 0-10Bar

Product characteristics
Number of inputs and outputs Number of digital outputs: 2
Measuring range
-1…10 bar -14.5…145 psi -0.1…1 MPa
Process connection threaded connection G 1/4 Internal thread
Application
System gold-plated contacts
Measuring element ceramic-capacitive pressure measuring cell
Application for industrial applications
Media liquids and gases
Medium temperature[°C] -25…80
Min. bursting pressure
150 bar 2175 psi 15 MPa
Pressure rating
75 bar 1087 psi 7.5 MPa
Vacuum resistance
-1000 mbar -0.1 MPa
Type of pressure relative pressure; vacuum
Electrical data
Operating voltage[V] 18…30 DC; (to SELV/PELV)
Current consumption[mA] < 35
Min. insulation resistance[MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time[s] < 0.3
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2
Outputs
Total number of outputs 2
Output signal switching signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / closed; (configurable)
Max. voltage drop switching output DC[V] 2.5
Permanent current rating of switching output DC[mA] 150; (200 (…60 °C) 250 (…40 °C))
Switching frequency DC[Hz] < 170
Short-circuit protection yes
Type of short-circuit protection yes (non-latching)
Overload protection yes
Measuring/setting range
Measuring range
-1…10 bar -14.5…145 psi -0.1…1 MPa
Factory setting / CMPT = 2
Set point SP
-0.9…10 bar -13.5…145 psi -0.09…1 MPa
Reset point rP
-0.95…9.95 bar -14…144.5 psi -0.095…0.995 MPa
Min. difference between SP and rP
0.05 bar 1 psi 0.005 MPa
In steps of
0.05 bar 0.5 psi 0.005 MPa
Status_B High Resolution / CMPT = 3
Set point SP
-0.92…10 bar -13.3…145 psi -0.092…1 MPa
Reset point rP
-0.97…9.95 bar -14…144.3 psi -0.097…0.995 MPa
Min. difference between SP and rP
0.05 bar 0.8 psi 0.005 MPa
In steps of
0.01 bar 0.1 psi 0.001 MPa